FGL's 3 bus Test System

Introduction

The FGL's Test Case represents a simple academic transmission system developed by Dr. Francisco M. Gonzalez-Longatt on April 2007.

Single line diagram of the FGL's 3-bus test system

You can send submissions, questions and requests to fglongatt@fglongatt.org.ve.

System Data

Sbase: 100 MVA Vbase: 115 kV

Transmission Line Data

From bus

To bus

MVA

r (p.u)

x (p.u)

BARRA_1

BARRA_2

100.0

0.040

0.0200

BARRA_1

BARRA_3

100.0

0.030

0.0100

BARRA_2

BARRA_3

100.0

0.025

0.0125

Generator Data

Bus

Type

Vg(p.u)

Pg (p.u)

Qmín (p.u)

Qmáx (p.u)

R’ (p.u)

X’ (p.u)

BARRA_1

2

1.05

2.163

0.0

0.0

0.0100

0.0300

BARRA_3

1

1.04

2.000

-0.2

0.4

0.0100

0.0300

Load Data Data

Bus

Type

load- PL (p.u)

Load - QL (p.u)

BARRA_1

Slack

0.0

0.0

BARRA_2

PQ

4.0

2.0

BARRA_3

PV

0.0

0.0

 

Admittance Matrix

 

 

 

 

Results of Admittance Matrix using PowerWorld: FGL's 3-bus test system

 

Power Flow Results

Power Flow Results of  FGL's 3-bus test system using PowerWorld

 

 

-- IMPORTANT -- Material in the archive is intended for purposes of research and education, not for commercial gain.

tEST cASES

viñeta

Single-Line diagram of the FGL's 3- bus System (56KB JPEG) (Small readable version)

viñeta

IEEE Common Data Format (CDF) [Download] [.txt File]

viñeta

DIigSILENT PowerFactory [Download]

viñeta

Powerworld [Download]

viñeta

Power System Toolbox (PST) [Donwload [Donwload]

viñeta

Power System Analysis Toolbox (PSAT) [Download]

 
Copyright © 2008-2013. All design and images are property of  Francisco M. González-Longatt. Web designed and developed by Dr. Francisco M. González-Longatt, e-mail: fglongatt@fglongatt.org