FGL's
3 bus Test SystemIntroduction
The FGL's Test Case represents a
simple academic transmission system developed by Dr. Francisco M.
Gonzalez-Longatt on April 2007.

Single line diagram of the FGL's 3-bus test system
You can
send submissions, questions and requests to
fglongatt@fglongatt.org.ve.
System Data
Sbase: 100
MVA Vbase: 115 kV
Transmission Line Data
|
From bus |
To bus |
MVA |
r (p.u) |
x (p.u) |
|
BARRA_1 |
BARRA_2 |
100.0 |
0.040 |
0.0200 |
|
BARRA_1 |
BARRA_3 |
100.0 |
0.030 |
0.0100 |
|
BARRA_2 |
BARRA_3 |
100.0 |
0.025 |
0.0125 |
Generator Data
|
Bus |
Type |
Vg(p.u) |
Pg (p.u) |
Qmín (p.u) |
Qmáx (p.u) |
R’ (p.u) |
X’ (p.u) |
|
BARRA_1 |
2 |
1.05 |
2.163 |
0.0 |
0.0 |
0.0100 |
0.0300 |
|
BARRA_3 |
1 |
1.04 |
2.000 |
-0.2 |
0.4 |
0.0100 |
0.0300 |
Load Data Data
|
Bus |
Type |
load-
PL (p.u) |
Load
- QL (p.u) |
|
BARRA_1 |
Slack |
0.0 |
0.0 |
|
BARRA_2 |
PQ |
4.0 |
2.0 |
|
BARRA_3 |
PV |
0.0 |
0.0 |
Admittance Matrix


Results of Admittance Matrix using PowerWorld: FGL's 3-bus test system
Power Flow Results

Power Flow Results of FGL's 3-bus test system using PowerWorld
tEST cASES

 |
Single-Line
diagram of the FGL's 3- bus System (56KB JPEG) (Small readable
version) |
 |
IEEE Common Data Format (CDF) [Download]
[.txt File] |
 |
DIigSILENT PowerFactory [Download] |
 |
Powerworld [Download] |
 |
Power System Toolbox (PST) [Donwload [Donwload] |
 |
Power System Analysis Toolbox (PSAT)
[Download] |
|
|